§192.115 Temperature derating factor (T) for steel pipe

Current as of Oct 29, 2026Last amended Dec 19, 2016Official text on eCFR ↗

The temperature derating factor to be used in the design formula in § 192.105 is determined as follows:

Gas temperature in degrees Fahrenheit (Celsius)Temperature derating factor (T)
250 °F (121 °C) or less1.000
300 °F (149 °C)0.967
350 °F (177 °C)0.933
400 °F (204 °C)0.900
450 °F (232 °C)0.867

For intermediate gas temperatures, the derating factor is determined by interpolation.

Source: 35 FR 13257, Aug. 19, 1970, as amended by Amdt. 192-85, 63 FR 37502, July 13, 1998

Compiled from the Electronic Code of Federal Regulations (eCFR), an editorial compilation and not an official legal edition of the CFR. The official text is the Federal Register and the annual CFR edition. §192.115 on eCFR.

Sections that cite this one